Common Name: HALOTRON I
Manufacturer: AMERICAN PACIFIC
SDS Revision Date: 2/2/2021
SDS Format: GHS-US
   
Item Number(s): 13J012, 13J013, 35WT18, 35WT19, 35WT22, 3YWK1, 3YWK4, 3YWK7, 3YWL1, 3YWL4
Manufacturer Model Number(s):



SDS Table of Contents
Click the desired link below to jump directly to that section in the SDS.
1. IDENTIFICATION 
2. HAZARDS IDENTIFICATION 
3. COMPOSITION/INFORMATION OR INGREDIENTS 
4. FIRST AID MEASURES 
5. FIRE FIGHTING MEASURES 
6. ACCIDENTAL RELEASE MEASURES 
7. HANDLING AND STORAGE 
8. EXPOSURE CONTROLS/PERSONAL PROTECTION 
9. PHYSICAL AND CHEMICAL PROPERTIES 
10. STABILITY AND REACTIVITY 
11. TOXICOLOGICAL INFORMATION 
12. ECOLOGICAL INFORMATION 
13. DISPOSAL CONSIDERATIONS 
14. TRANSPORT INFORMATION 
15. REGULATORY INFORMATION 
16. OTHER INFORMATION 



HALOTRON I SAFETY DATA SHEET

SAFETY DATA SHEET


1. IDENTIFICATION 


PRODUCT NAME: HALOTRON(R*) I

SYNONYM: CLEAN AGENT / HCFC BLEND B, HALOTRON(R*) I PRE-SAT BASE

SDS COMPLIANT WITH REGULATIONS:
(EC) NO 1907/2006 (REACH), (EC) NO 1272/2008 (CLP)

DISTRIBUTOR: BUCKEYE FIRE EQUIPMENT

COMPANY ADDRESS:
110 KINGS ROAD
KINGS MOUNTAIN, NC 28086

TELEPHONE: 704-739-7415

WEB ADDRESS: WWW.BUCKEYEFIRE.COM

MANUFACTURER:
AMERICAN PACIFIC CORPORATION
HALOTRON DIVISION 10622 WEST 6400 NORTH
CEDAR CITY, UT 84721

TELEPHONE: 435-865-5000

FAX: 435-865-5005

EMAIL: SDS@APFC.COM

RECOMMENDED USE:
FIRE SUPPRESSION, NON-RESIDENTIAL, NOT FOR HUMAN OR ANIMAL DRUG USE.

EMERGENCY:
CHEMTREC: 1.800.424.9300
CUSTOMER NUMBER: CCN21187

REVISION DATE: 03/2019

USE OF SUBSTANCE/PREPARATION:
HALOTRON(R*) I IS A CLEAN FIRE-EXTINGUISHING AGENT FOR STREAMING AND LOCAL
APPLICATIONS. NFPA 2001, "STANDARD ON CLEAN AGENT FIRE EXTINGUISHING
SYSTEMS" DEFINES A "CLEAN AGENT" TO BE "ELECTRICALLY NON-CONDUCTING,
VOLATILE, OR GASEOUS FIRE EXTINGUISHANT THAT DOES NOT LEAVE A RESIDUE
UPON EVAPORATION." HALOTRON(R*) I IS A SAFE, EFFECTIVE, ENVIRONMENTALLY
ACCEPTABLE CLEAN AGENT. IT IS DISCHARGED AS A LIQUID, WHICH RAPIDLY
EVAPORATES (I.E. IT IS VOLATILE). IT IS A PROPRIETARY THREE COMPONENT
CHEMICAL BLEND BASED ON HCFC-123 THAT HAS BEEN FOUND ACCEPTABLE BY THE
U.S. EPA UNDER ITS SIGNIFICANT NEW ALTERNATIVES POLICY (SNAP) PROGRAM
(REFERRED TO AS "HCFC BLEND B") FOR ALL NON-RESIDENTIAL USE (INCLUDING
COMMERCIAL/INDUSTRIAL, MILITARY, AND MARITIME USE) IN STREAMING
APPLICATIONS AS A SUBSTITUTE FOR HALON 1211 (BROMOCHLORODIFLUOROMETHANE
OR "BCF").


2. HAZARDS IDENTIFICATION 


HAZARD CLASSIFICATION:
SPECIFIC TARGET ORGAN TOXICITY, SINGLE EXPOSURE - CATEGORY 3
GASES UNDER PRESSURE - DISSOLVED GAS

PICTOGRAM:
EXCLAMATION MARK
GAS CYLINDER

SIGNAL WORD: WARNING

PREPARATION CLASSIFICATION:

PHYSICAL HAZARD:
H280: CONTAINS GAS UNDER PRESSURE; MAY EXPLODE IF HEATED

HEALTH HAZARD:
H336: MAY CAUSE DROWSINESS AND DIZZINESS

PRECAUTIONARY STATEMENTS:
P261: AVOID BREATHING VAPORS/SPRAY

P271: USE ONLY OUTDOORS OR IN A WELL-VENTILATED AREA

P304+P340:
IF INHALED: REMOVE PERSON TO FRESH AIR AND KEEP COMFORTABLE FOR BREATHING

P 312: CALL A POISON CENTER OR DOCTOR/PHYSICIAN IF YOU FEEL UNWELL

P403+P233:
STORE IN A WELL-VENTILATED PLACE. KEEP CONTAINER TIGHTLY CLOSED.

P405: STORE LOCKED UP

P501: DISPOSE OF CONTENTS/CONTAINER TO AN APPROVED WASTE DISPOSAL PLANT

INFORMATION PERTAINING TO PARTICULAR DANGERS FOR MAN AND ENVIRONMENT:
INHALATION OF HIGH CONCENTRATIONS OF VAPOUR MAY CAUSE CENTRAL NERVOUS
SYSTEM EFFECTS SUCH AS DIZZINESS, DROWSINESS, ANESTHESIA, OR
UNCONSCIOUSNESS. WHEN USED ON A FIRE, HAZARDOUS DECOMPOSITION PRODUCTS
ARE FORMED, BUT TYPICALLY ARE WITHIN SAFE EMERGENCY EXPOSURE LIMITS.
MISUSE OR INTENTIONAL INHALATION ABUSE MAY LEAD TO DEATH WITHOUT WARNING.


3. COMPOSITION/INFORMATION OR INGREDIENTS 


INGREDIENT   CHEMICAL MAKEUP       CAS#       EC#        %
NAME

HCFC-123     2, 2-DICHLORO-1, 1,   306-83-2   206-190-3  GREATER THAN 93%
             1-TRIFLUOROETHANE

GAS MIXTURE  PROPRIETARY                                 LESS THAN 7%


4. FIRST AID MEASURES 


AS A GENERAL RULE, IN CASE OF DOUBT OR IF SYMPTOMS PERSIST, ALWAYS CALL
A PHYSICIAN

ROUTES OF    SIGNS AND SYMPTOMS OF            EMERGENCY AND FIRST AID
EXPOSURE     EXPOSURE                         PROCEDURES

SKIN         EVAPORATIVE COOLING CAN RESULT   WASH EXPOSED AREA WITH
             IN CHILLING SENSATIONS OR        WATER. IF IRRITATION
             FROSTBITE EFFECTS. SHORT         DEVELOPS AND PERSISTS,
             EXPOSURES, SUCH AS WHEN          CALL A PHYSICIAN.
             FILLING EQUIPMENT OR IN
             OTHER SITUATIONS, SHOULD NOT
             HAVE A LASTING EFFECT.

INHALATION   SIGNIFICANT EXPOSURE MAY CAUSE   REMOVE TO FRESH AIR. OXYGEN
             CENTRAL NERVOUS SYSTEM EFFECTS   OR ARTIFICIAL RESPIRATION
             SUCH AS DIZZINESS, DROWSINESS,   IF NECESSARY
             ANESTHESIA, OR UNCONSCIOUSNESS.

             HIGH CONCENTRATIONS OF 20,000    CALL A PHYSICIAN IF
             PPM (V/V) OR HIGHER, MAY CAUSE   BREATHING DIFFICULTIES
             CARDIAC ARRHYTHMIA.              OCCUR.

INGESTION    NOT LIKELY TO OCCUR IN           CLEAN MOUTH WITH WATER AND
             INDUSTRIAL USE. HIGHLY           DRINK PLENTY OF WATER. DO
             VOLATILE LIQUID.                 NOT INDUCE VOMITING. IF
                                              VOMITING OCCURS, LEAN PERSON
                                              FORWARD TO REDUCE RISK OF
                                              ASPIRATION. CALL A
                                              PHYSICIAN.

EYES         IRRITATION AND TEARING MAY       RINSE THOROUGHLY WITH PLENTY
             RESULT. MILD TO MODERATE         OF WATER, ALSO UNDER THE
             REVERSIBLE EYE EFFECTS.          EYELIDS. IF EYE IRRITATION
                                              PERSISTS, CONSULT A
                                              SPECIALIST.

DESCRIPTION OF THE MOST IMPORTANT SYMPTOMS OR EFFECTS:
HALOTRON(R*) I IS A COLORLESS VOLATILE, PRESSURIZED LIQUID WITH A SLIGHT
ETHER-LIKE ODOR. AS WITH ANY CHEMICAL, DOSE AND EXPOSURE ARE CRITICALLY
IMPORTANT VARIABLES TO UNDERSTAND ANY POTENTIAL TREATMENT. SHORT-TERM
EXPOSURE TO HIGH CONCENTRATIONS MAY RESULT IN CENTRAL NERVOUS SYSTEM
AND CARDIAC EFFECTS. LONG-TERM EXPOSURE TO CONCENTRATIONS ABOVE THOSE
TIME-WEIGHTED AVERAGES RECOMMENDED HEREIN MAY RESULT IN LIVER EFFECTS.

NOTE TO PHYSICIAN:
THIS MATERIAL MAY MAKE THE HEART MORE SUSCEPTIBLE TO ARRHYTHMIAS.
CATECHOLAMINES SUCH AS ADRENALINE, AND OTHER COMPOUNDS HAVING SIMILAR
EFFECTS, SHOULD BE RESERVED FOR EMERGENCIES AND THEN USED ONLY WITH
SPECIAL CAUTION.


5. FIRE FIGHTING MEASURES 


FLAMMABLE PROPERTIES:

FLASH POINT: NOT FLAMMABLE.

FLASH POINT METHOD: NOT APPLICABLE.

AUTO-IGNITION TEMPERATURE: NOT DETERMINED.

UPPER FLAMMABILITY LIMIT (VOLUME % IN AIR): NOT APPLICABLE.
LOWER FLAMMABILITY LIMIT (VOLUME % IN AIR): NOT APPLICABLE.

EXTINGUISHING MEDIA:
THE PROPERTIES OF THIS CHEMICAL MAKE IT AN IDEAL EXTINGUISHING MEDIA
ITSELF.

SPECIAL FIREFIGHTING PRECAUTIONS/INSTRUCTIONS:
ENSURE THAT THE AREA WHERE THE FIRE OCCURRED IS WELL VENTILATED BEFORE
RE-ENTERING. WEAR PROTECTIVE CLOTHING. USE WATER SPRAY OR FOG TO COOL
STORAGE CONTAINERS TO HELP PREVENT AN UNCONTROLLED PRESSURE RELEASE.
SUITABLE EXTINGUISHING MEDIA: USE EXTINGUISHING MEASURES THAT ARE
APPROPRIATE TO LOCAL CIRCUMSTANCES AND THE SURROUNDING ENVIRONMENT.

UNSUITABLE EXTINGUISHING MEDIA: NONE.

UNUSUAL FIRE AND EXPLOSION HAZARDS:
THE CONCENTRATED AGENT WHEN APPLIED TO FIRE CAN PRODUCE TOXIC BY-PRODUCTS
SPECIFICALLY HYDROGEN HALIDES, WHICH CAN CAUSE DAMAGE. AVOID INHALATION
OF THESE MATERIALS BY EVACUATING AND VENTILATING THE AREA.


6. ACCIDENTAL RELEASE MEASURES 


IN CASE OF SPILL OR OTHER RELEASE:
PREVENT FURTHER LEAKAGE OR SPILLAGE IF SAFE TO DO SO. KEEP AWAY FROM
INCOMPATIBLE PRODUCTS. IN THE EVENT OF A LARGE SPILL, ALLOW FOR ADEQUATE
VENTILATION, AND DO NOT RE-ENTER AN AREA WITHOUT A SELF-CONTAINED
BREATHING APPARATUS (SCBA) UNTIL ADEQUATE VENTILATION IS ACCOMPLISHED.
FOR SPILLS THAT MIGHT RESULT IN OVEREXPOSURE, EVACUATE THE AREA AND USE
PROTECTIVE GEAR AND SCBA'S. AVOID LEAKAGE INTO WATERWAYS. THE VAPOURS
ARE HEAVIER THAN AIR; THEREFORE USE CAUTION WHEN LARGE VOLUME RELEASES
OCCUR IN LOW-LYING AREAS WHERE CONCENTRATED VAPORS MAY ACCUMULATE.

RECOMMENDED 1 HR. EMERGENCY EXPOSURE LIMIT:
1000 PPM (V/V) ON THE SAME BASIS AS ABOVE

RECOMMENDED 1 MIN. EMERGENCY EXPOSURE LIMIT:
2500 PPM (V/V) ON THE SAME BASIS AS ABOVE

ADVICE FOR EMERGENCY RESPONDERS (LARGE SPILLS):
IMMEDIATELY EVACUATE PERSONNEL TO SAFE AREAS. KEEP PEOPLE AWAY FROM AND
UPWIND OF SPILL/LEAK. WEAR SCBA AND PROTECTIVE SUIT. THE PRODUCT
EVAPORATES READILY. VENTILATE THE AREA.

ENVIRONMENTAL PRECAUTIONS:
PREVENT MATERIAL FROM ENTERING INTO WATERWAYS, SOIL OR DRAINS.

METHODS AND MATERIALS FOR CONTAINMENT AND CLEANING UP:
DAM UP. SOAK UP WITH INERT ABSORBENT MATERIAL. PREVENT PRODUCT FROM
ENTERING DRAINS. KEEP IN PROPERLY LABELLED CONTAINERS. KEEP IN SUITABLE,
CLOSED CONTAINERS FOR DISPOSAL. REFER TO OTHER SECTIONS AND TO PROTECTIVE
MEASURES LISTED IN SECTION 8.

ANY FOOD ITEMS THAT WERE DIRECTLY SPRAYED BY THE LIQUID SHOULD BE THROWN
AWAY, AND ALL SURFACES THAT ARE USED FOR FOOD SERVICE SHOULD BE WASHED
(AS NORMAL) BEFORE RE-USE.

WASTE DISPOSAL:
OBSERVE ALL FEDERAL, STATE, AND LOCAL REGULATIONS FOR PRODUCTS OF THIS
TYPE WHEN ACCOMPLISHING DISPOSAL

SUPPLIER NOTIFICATION:
(SECTION 313 ) THIS PRODUCT CONTAINS MORE THAN 93% BY WEIGHT
2,2-DICHLORO-1,1,1- TRIFLUOROETHANE (CAS #306-83-2) WHICH IS SUBJECT TO
THE REPORTING REQUIREMENTS OF SECTION 313 OF THE EMERGENCY PLANNING AND
COMMUNITY RIGHT-TO-KNOW ACT OF 1986 (40CFR372).


7. HANDLING AND STORAGE 


NORMAL HANDLING:
PRECAUTIONS FOR SAFE HANDLING - TRANSFER MATERIAL IN A CLOSED SYSTEM.
HANDLE ONLY IN WELL- VENTILATED AREAS. USE ONLY EQUIPMENT AND MATERIALS
WHICH ARE COMPATIBLE WITH THE PRODUCT.

CONDITIONS FOR STORAGE, INCLUDING INCOMPATIBILITIES: KEEP CONTAINER CLOSED

SPECIFIC USE(S):
FOR FURTHER INFORMATION, PLEASE CONTACT: SUPPLIER

ADDITIONAL NOTE:
APPROVED DOT SHIPPING CONTAINERS ARE A NORMAL SAFE METHOD OF STORAGE.
CONTAINERS SHOULD BE MAINTAINED IN GOOD CONDITION. DO NOT ALLOW MATERIAL
TO REMAIN IN DETERIORATING CONTAINERS. BECAUSE THIS PRODUCT CAN
VOLATILIZE, SPECIAL CARE SHOULD BE TAKEN FOR OVER PRESSURIZATION HAZARDS
IF THE CONTAINERS ARE OVERHEATED OR NEAR A RADIANT HEAT SOURCE.


8. EXPOSURE CONTROLS/PERSONAL PROTECTION 


ENGINEERING CONTROLS:
VENTILATE AS NECESSARY TO MINIMIZE EXPOSURE LEVELS. INSPECT AND CLEAN
VENTILATION SYSTEMS REGULARLY. PROLONGED USE SHOULD OCCUR ONLY IN AREAS
WITH ADEQUATE VENTILATION. KEEP STORAGE CONTAINERS TIGHTLY CLOSED. VAPORS
ARE HEAVIER THAN AIR POSING A POTENTIAL HAZARD IF LARGE VOLUMES ARE
TRAPPED IN ENCLOSED OR LOW PLACES.

PERSONAL PROTECTIVE EQUIPMENT:
PROTECTIVE SHOES, SUCH AS STEEL TOED SHOES, SHOULD BE WORN IN ADDITION TO
THE OTHER SPECIFIED PERSONAL PROTECTIVE EQUIPMENT (PPE) WHEN HANDLING BULK
CONTAINERS. IF HANDLING BULK MATERIAL OR TRANSFERRING THE MATERIAL FROM
FIRE PROTECTION EQUIPMENT, WEAR SAFETY GLASSES WITH SIDE SHIELDS. THIS
STATEMENT IS NOT INTENDED TO APPLY TO USE OF A FIRE EXTINGUISHER WHERE
THE NOZZLE ARRANGEMENT IS INTENDED TO DIRECT THE DISCHARGE AWAY FROM THE
USER OF THE EXTINGUISHER. WEAR PROTECTIVE CLOTHING WHEN HANDLING A LEAK IN
A STORAGE CONTAINER (DOES NOT APPLY TO FIRE PROTECTION EQUIPMENT
SERVICING, OTHER THAN SAFETY GOGGLES AND GLOVES IF LARGE VOLUMES CAN BE
EXPOSED TO SKIN). SHORT EXPOSURES TO SKIN ARE NOT LIKELY TO POSE A HAZARD.
RESPIRATORY PROTECTION IS NOT NORMALLY NEEDED, HOWEVER, IF HANDLED IN
ENCLOSED SPACES WHERE APPLICABLE EXPOSURE LIMITS MIGHT BE EXCEEDED, A
SCBA SHOULD BE USED. WHEN PERFORMING FILLING OR SERVICING OPERATIONS,
PERFORM THESE ACTIVITIES IN A WELL- VENTILATED AREA

TIME WEIGHTED EXPOSURE LIMITS: (FOR PERSONS REGULARLY EXPOSED TO MATERIAL)

WORKPLACE ENVIRONMENTAL EXPOSURE LEVEL, WEEL (AIHA) (8 HRS.):
50 PPM (V/V), BASED ON THE PRIMARY COMPONENT (HCFC-123)


9. PHYSICAL AND CHEMICAL PROPERTIES 


APPEARANCE: PRESSURIZED, COLORLESS,

PHYSICAL STATE: LIQUID

MOLECULAR WEIGHT: APPROX. 150.7

CHEMICAL FORMULA: CF3CHCl2 PLUS PROPRIETARY GAS MIXTURE

ODOR: SLIGHT ETHER-LIKE ODOR

SPECIFIC GRAVITY (WATER = 1.0): 1.47 AT 25 DEG. C (77 DEG. F)

SOLUBILITY IN WATER: 0.39% WT. @ 25 DEG. C (77 DEG. F), 1 ATM

PH: NOT APPLICABLE

BOILING POINT: 27 DEG. C (80.6 DEG. F)

MELTING POINT: NOT APPLICABLE

RELATIVE DENSITY, AIR = 1: 5.1

PARTITION COEFFICIENT, N-OCTANOL/WATER, LOG POW: 2.0 - 2.8

AUTO-IGNITION TEMPERATURE: NOT DETERMINED

UPPER FLAMMABILITY OR EXPLOSIVE LIMITS: NOT APPLICABLE
LOWER FLAMMABILITY OR EXPLOSIVE LIMITS: NOT APPLICABLE

VAPOR PRESSURE AT: 655 KPA (95 PSIG) AT 20 DEG. C (70 DEG. F)

VAPOR DENSITY: APPROX. 6.08 KG/M3 (0.387 LB./FT3) AT 25 DEG. C (77 DEG. F)

EVAPORATION RATE: FASTER THAN WATER, SLOWER THAN ETHER

FLASH POINT: NONE

LIQUID DENSITY: 1.48 KG/L (92.3 LB./FT3) AT 25 DEG. C (77 DEG. F)


10. STABILITY AND REACTIVITY 


REACTIVITY: DECOMPOSES ON HEATING.

CHEMICAL STABILITY:
NORMALLY STABLE (WILL DECOMPOSE IF EXPOSED TO A HIGH RADIANT HEAT SOURCE,
SUCH AS FIRE). THE MATERIAL IS INTENDED FOR USE AS A FIRE EXTINGUISHANT.

INCOMPATIBILITIES:
INCOMPATIBLE WITH ALKALI OR ALKALINE EARTH METALS, AND POWDERED METALS
Al, Zn, Be, ETC.

HAZARDOUS DECOMPOSITION PRODUCTS:
DECOMPOSITION PRODUCTS ARE HAZARDOUS. THIS MATERIAL CAN BE DECOMPOSED BY
HIGH TEMPERATURES (OPEN FLAMES, GLOWING METAL SURFACES, ETC.) FORMING
HYDROCHLORIC AND HYDROFLUORIC ACIDS, AND POSSIBLY CARBONYL HALIDE.

HAZARDOUS POLYMERIZATION: WILL NOT OCCUR


11. TOXICOLOGICAL INFORMATION 


TOXICOLOGICAL INFORMATION: ACUTE TOXICITY IS LOW.

FOR 2,2-DICHLORO-1,1,1-TRIFLUOROETHANE (CAS # 306-83-2):

LC50 (4 HR.): 3.2% (32,000 PPM), (INHALATION)

ORAL APPROXIMATE LETHAL DOSE (ALD): 9 G/KG (BODY WEIGHT)

CARDIOTOXIC LOAEL (LOWEST OBSERVED ADVERSE EFFECT LEVEL): 2%VOL.

CARDIOTOXIC NOAEL (NO OBSERVED ADVERSE EFFECT LEVEL): 1%VOL.

TOXICOLOGICAL TESTING WAS PERFORMED ON HCFC-123 BY THE PROGRAM FOR
ALTERNATIVE FLUOROCARBON TESTING (PAFT). DATA FROM ACUTE TOXICITY STUDIES
IN THIS PROGRAM DEMONSTRATED THAT HCFC-123 HAS VERY LOW TOXICITY BY SKIN
APPLICATION OR INHALATION.

FOR THE PROPRIETARY GAS MIXTURE:
THE TOXIC EFFECTS OF THE PROPRIETARY GAS MIXTURE IN THE ABSENCE OF EXTREME
TEMPERATURE ARE PRIMARILY ITS ABILITY TO FUNCTION AS A SIMPLE ASPHYXIANT
(I.E. DISPLACE OXYGEN).

OTHER TOXICITY INFORMATION:

ANIMAL STUDIES:

FOR 2,2-DICHLORO-1,1,1-TRIFLUOROETHANE (CAS #306-83-2):
LONG-TERM EXPOSURE IN A TWO YEAR STUDY (6 HOURS/DAY, 5 DAYS/WEEK) AT
CONCENTRATIONS OF 300, 1000 AND 5000 PPM DECREASED BODY WEIGHT, SERUM
CHOLESTEROL, TRIGLYCERIDES AND GLUCOSE, AND INCREASED URINARY FLUORIDE
CONCENTRATIONS IN RATS. HOWEVER, SURVIVAL WAS SIGNIFICANTLY IMPROVED IN
ALL EXPOSED GROUPS COMPARED TO CONTROL ANIMALS. INHALATION OF 300, 1000
AND 5000 PPM CAUSED AN INCREASE IN BENIGN TUMORS OF THE LIVER, PANCREAS,
AND TESTIS. TUMORS OCCURRED LATE IN LIFE AND NONE WERE ASSESSED TO BE LIFE
THREATENING. TUMOR FORMATION IS THOUGHT TO OCCUR THROUGH NON-GENOTOXIC
MECHANISMS ASSOCIATED WITH A PEROXISOME PROLIFERATING POTENTIAL OR WITH
HORMONAL DISTURBANCES IN OLDER RATS.

EXPOSURE TO DOGS, GUINEA PIGS OR MONKEYS AT 1000 PPM OR GREATER FOR 6
HOURS PER DAY,7 DAYS PER WEEK, FOR A TOTAL OF 3 WEEKS, INDUCED SLIGHT OR
MILD LIVER DAMAGE WITH ALTERED ENZYME LEVELS.

RODENT STUDIES INDICATE HCFC-123 IS EASILY ABSORBED VIA INHALATION. IT
DISTRIBUTES IN ALL ORGANS, MORE SO IN THE LIVER. ABOUT 90% OF INHALED
HCFC-123 IS ELIMINATED VIA THE LUNGS UNCHANGED. THE REMAINING AMOUNT IS
METABOLIZED TO TRIFLUOROACETIC ACID AND EXCRETED IN THE URINE. SMALL
AMOUNTS OF TRIFLUOROACETYLATED PROTEINS WERE DETECTED IN RATS IN
LABORATORY STUDIES.

HCFC-123 DID NOT AFFECT REPRODUCTIVE PERFORMANCE IN RATS OR HARM THE
UNBORN ANIMALS IN RATS OR RABBITS AT 5000 AND 10,000 PPM.

HCFC-123 WAS INACTIVE IN SEVERAL TEST-TUBE GENETIC DAMAGE STUDIES EXCEPT
THE HUMAN LYMPHOCYTE CHROMOSOME ABERRATION ASSAY. HCFC-123 IS ALSO
INACTIVE IN LIVE ANIMAL GENETIC DAMAGE STUDIES. THEREFORE, IT IS NOT
CONSIDERED GENOTOXIC.

CARCINOGEN:
IARC: NO
NTP: NO
OSHA: NO


12. ECOLOGICAL INFORMATION 


AQUATIC TOXICITY:
2,2-DICHLORO-1,1,1-TRIFLUOROETHANE (HCFC-123)
96 H LC50: ONCORHYNCHUS MYKISS (RAINBOW TROUT) 55.5 MG/L
96 H ERC50: PSEUDOKIRCHNERIELLA SUBCAPITATA (GREEN ALGAE) 96.6 MG/L
96 H EBC50: PSEUDOKIRCHNERIELLA SUBCAPITATA (GREEN ALGAE) 67.8 MG/L
48 H EC50: DAPHNIA MAGNA (WATER FLEA) 17.3 MG/L

ENVIRONMENTAL FATE:

2,2-DICHLORO-1,1,1-TRIFLUOROETHANE (HCFC-123)

BIODEGRADABILITY: 24%, NOT READILY BIODEGRADABLE

BIOACCUMULATION:
BIO-CONCENTRATION FACTOR (BCF): 33, BIOACCUMULATION IS UNLIKELY

THE MATERIAL IS A MIXTURE OF VOLATILE ORGANIC COMPOUNDS (ALTHOUGH
EXEMPTED FROM REPORTING AS A VOC UNDER U.S. REGULATION 40 CFR PART
51.100(S)) AND SHOULD NOT BE PERMITTED TO BE MIXED WITH GROUND OR
DRINKING WATER AND SHOULD BE HANDLED, USED, AND DISPOSED RESPONSIBLY
IN ACCORDANCE WITH REGULATIONS IN THE COUNTRY, PROVINCE, STATE, COUNTY,
AND LOCALITY WHERE IT IS USED.


13. DISPOSAL CONSIDERATIONS 


OBSERVE ALL FEDERAL, STATE, AND LOCAL REGULATIONS FOR PRODUCTS OF THIS
TYPE WHEN ACCOMPLISHING DISPOSAL.

THE MANUFACTURER ASSUMES NO LIABILITY FOR THE USE OF THIS PRODUCT IN A
MANNER THAT CAUSES ENVIRONMENTAL OR OTHER HARM.


14. TRANSPORT INFORMATION 


UN NUMBER: UN1956

PROPER SHIPPING NAME:
UN1956, COMPRESSED GAS, N.O.S., 2.2 (CONTAINS ARGON, TETRAFLUOROMETHANE)

US DOT HAZARD CLASS: 2.2, NONFLAMMABLE GAS

PACK GROUP: N/A

FIREEXTINGUISHERS:

UN NUMBER: UN1044

PROPER SHIPPING NAME: FIRE EXTINGUISHERS

US DOT HAZARD CLASS: 2.2

PACK GROUP: N/A

THE PROPER SHIPPING NAME SHALL BE FIRE EXTINGUISHER, THE UN IDENTIFICATION
NUMBER IS UN 1044, AND THE USDOT HAZARD CLASS IS LIMITED QUANTITY WHEN
PRESSURIZED TO LESS THAN 241 PSIG AND WHEN SHIPPED VIA HIGHWAY OR RAIL.
USE CLASS 2.2, NON- FLAMMABLE GAS, WHEN SHIPPING VIA AIR OR MARINE.


15. REGULATORY INFORMATION 


LISTED IN THE TOXIC SUBSTANCES CONTROL ACT (TSCA) INVENTORY:
YES, ALL COMPONENTS ARE ON THE TSCA INVENTORY, LISTED ON EPA SARA (313)
HAZARD CLASS, AND IS SUBJECT TO REPORTING REQUIREMENTS OF EPCRA SECTION
313

HCFC-123 IS LISTED UNDER EINECS EC NUMBER 206-190-3 FOR INTERMEDIATE
USE ONLY.

ALL COMPONENTS OF THE PROPRIETARY GAS MIXTURE ARE LISTED IN EINECS BASED
ON ESIS LOOKUP FOR THE EUROPEAN UNION.

THIS CHEMICAL SUBSTANCE IS NOT CLASSIFIED IN THE ANNEX I OF DIRECTIVE
67/548/EEC.

IT IS LISTED AS A LPV FOR CANADA, ALL COMPONENTS LISTED IN CANADIAN DSL

INFORMATION ABOUT LIMITATION OF USE:
THIS BLEND IS INTENDED SOLELY FOR USE AS A FIRE EXTINGUISHING AGENT AND
SHOULD NOT BE USED FOR OTHER PURPOSES WITHOUT CONTACT AND TECHNICAL
DISCUSSION WITH THE MANUFACTURER.

THIS PREPARATION WAS CLASSIFIED IN COMPLIANCE WITH THE FOLLOWING
DIRECTIVES AND REGULATIONS:
(EC) NO 1907/2006 (REACH)
(EC) NO 1272/2008 (CLP)
(EC) NO 453/2010


16. OTHER INFORMATION 


THE USER IS RESPONSIBLE TO EVALUATE THE SAFETY AND ENVIRONMENTAL
CONSEQUENCES OF ANY INTENDED USES. THE MANUFACTURER ASSUMES NO
LIABILITY FOR ANY USAGES THAT RESULT IN ADVERSE CONSEQUENCES.

HAZARDOUS MATERIALS IDENTIFICATION SYSTEM (HMIS) RATINGS (SCALE 0 - 4):
HEALTH HAZARD 1
FIRE HAZARD   0
REACTIVITY    1
PPE           X

X - CONSULT YOUR SUPERVISOR OR S.O.P. FOR SPECIAL HANDLING DIRECTIONS

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) RATINGS (SCALE 0 - 4):
1
0
1

IMPORTANT:

IMPORTANT:
THE INFORMATION PRESENTED HEREIN, WHILE NOT GUARANTEED, WAS PREPARED BY
COMPETENT TECHNICAL PERSONNEL AND IS TRUE AND ACCURATE TO THE BEST OF OUR
KNOWLEDGE. NO WARRANTY OR GUARANTEE, EXPRESS OR IMPLIED, IS MADE REGARDING
PERFORMANCE, STABILITY OR OTHERWISE. THIS INFORMATION IS NOT INTENDED TO
BE ALL-INCLUSIVE AS TO THE MANNER AND CONDITIONS OF USE, HANDLING AND
STORAGE. OTHER FACTORS MAY INVOLVE OTHER OR ADDITIONAL SAFETY OR
PERFORMANCE CONSIDERATIONS. WHILE OUR TECHNICAL PERSONNEL WILL BE HAPPY TO
RESPOND TO QUESTIONS REGARDING SAFE HANDLING AND USE PROCEDURES, SAFE
HANDLING AND USE REMAINS THE RESPONSIBILITY OF THE CUSTOMER. NO
SUGGESTIONS FOR USE ARE INTENDED AS, AND NOTHING HEREIN SHALL BE
CONSTRUED AS A RECOMMENDATION TO INFRINGE ANY EXISTING PATENTS OR
VIOLATE ANY FEDERAL, OTHER NATIONAL GOVERNMENTAL ENTITY, STATE,
PROVINCIAL, OR LOCAL LAWS.

REV: 19

EFFECTIVE REVISION DATE: 2 FEBRUARY 2021