Common Name: VALVE REGULATED LEAD ACID BATTERY
Manufacturer: CSB BATTERY TAIWAN
SDS Revision Date: 6/22/2016
SDS Format: GHS-EU
   
Item Number(s): 429J03, 429J04, 429J05, 429J06, 429J07, 429J08, 429J09, 43MJ60
Manufacturer Model Number(s):



SDS Table of Contents
Click the desired link below to jump directly to that section in the SDS.
SECTION 1: IDENTIFICATION OF THE SUBSTANCE/MIXTURE 
SECTION 2: HAZARDS IDENTIFICATION 
SECTION 3: COMPOSITION/INFORMATION ON INGREDIENTS(2) 
SECTION 4: FIRST AID MEASURES 
SECTION 5: FIREFIGHTING MEASURES 
SECTION 6: ACCIDENTAL RELEASE MEASURES 
SECTION 7: HANDLING AND STORAGE 
SECTION 8: EXPOSURE CONTROLS/PERSONAL PROTECTION 
SECTION 9: PHYSICAL AND CHEMICAL PROPERTIES 
SECTION 10: STABILITY AND REACTIVITY 
SECTION 11: TOXICOLOGICAL INFORMATION 
SECTION 12: ECOLOGICAL INFORMATION 
SECTION 13: DISPOSAL CONSIDERATIONS 
SECTION 14: TRANSPORT INFORMATION 
SECTION 15: REGULATORY INFORMATION 
SECTION 16: OTHER INFORMATION 



CSB BATTERY

SDS (SAFETY DATA SHEET)

UPDATED: 2016/06/22


SECTION 1: IDENTIFICATION OF THE SUBSTANCE/MIXTURE 

                      AND OF THE COMPANY/UNDERTAKING

1.1 PRODUCT IDENTIFIER:

TRADE NAME/DESIGNATION: VALVE REGULATED LEAD ACID BATTERY

1.2 RELEVANT IDENTIFIED USES OF THE SUBSTANCE OR MIXTURE AND USES ADVISED
AGAINST:

RELEVANT IDENTIFIED USES: RECHARGEABLE STORAGE BATTERIES

1.3 DETAILS OF THE SUPPLIER:

MANUFACTURERS NAME: CSB BATTERY CO., LTD.

WEBSITE: HTTP://WWW.CSB-BATTERV.COM

RELEVANT IDENTIFIED USES: RECHARGEABLE STORAGE BATTERIES

INFORMATION CONTACT:
11F, NO. 150, SEC. 4, CHENGDE RD., SHILIN DIST., TAIPEI CITY 11167, TAIWAN

IMPORTERS NAME:

WEBSITE:

INFORMATION CONTACT:

1.4 EMERGENCY TELEPHONE NUMBER:

CONTACT NUMBER:
TAIWAN: +886 2 2880 5600
UNITED STATES: +1 817 244 7777
EUROPE, MIDDLE EAST, AFRICA: +31 0 180 418 140
CHINA: +86 755 8831 6488
AUSTRALIA:


SECTION 2: HAZARDS IDENTIFICATION 


CLASSIFICATION OF THE SUBSTANCE OR MIXTURE ACCORDING TO REGULATION (EC) NO
1272/2008 [CLP/GHS]:
MATERIAL IS AN ARTICLE. NO HEALTH EFFECTS ARE EXPECTED DURING NORMAL USE OF
THIS PRODUCT AS SOLD. HAZARDOUS EXPOSURE MAY OCCUR WHEN THE PRODUCT IS
HEATED, OXIDIZED OR OTHERWISE PROCESSED, DAMAGED OR SUBJECTED TO MISUSE.
FOLLOW MANUFACTURER'S INSTRUCTIONS FOR INSTALLATION, SERVICE AND USE.

HEALTH:

GHS    HAZARD CLASS/CATEGORY         HAZARD         2008/98/EC  LABELS
CODE                                 STATEMENTS     CODE

H302   ACUTE TOXICITY   CATEGORY 4   HARMFUL IF     HP 6        CORROSION
       (ORAL)                        SWALLOWED

H314   SKIN CORROSION   CATEGORY 1A  CAUSES SEVERE  HP 8        EXCLAMATION
                                     SKIN BURNS                 MARK
                                     AND EYE
                                     DAMAGE

H335   SPECIFIC TARGET  CATEGORY 3   MIGHT CAUSE    HP 5        HEALTH
       ORGAN TOXICITY,               RESPIRATORY                HAZARD
       SINGLE                        IRRITATION
       EXPOSURE,
       RESPIRATORY
       TRACT
       IRRITATION

H361   REPRODUCTIVE     CATEGORY 2   SUSPECTED      HP 10
       TOXICITY                      DAMAGING OF
                                     FERTILITY
                                     OR THE
                                     UNBORN CHILD

ENVIRONMENT:

GHS    HAZARD CLASS/CATEGORY         HAZARD         2008/98/EC  LABELS
CODE                                 STATEMENTS     CODE

H 411  HAZARDOUS TO     CATEGORY 2   TOXICITY TO    HP 14       ENVIRONMENT
       THE AQUATIC                   AQUATIC LIFE
       ENVIRONMENT,                  WITH LONG
       ACUTE HAZARD                  LASTING
                                     EFFECT

PHYSICAL:
UNDER ABNORMAL USE IN NOT VENTILATED ROOMS MAY FORM EXPLOSIVE AIR/GAS
MIXTURE DURING CHARGING OR WHEN EXTREME OVERCHARGING / EXTREMELY FLAMMABLE
GAS (HYDROGEN) / EXPLOSIVE, FIRE, BLAST OR PROJECTION HAZARD.

GHS    HAZARD CLASS/CATEGORY         HAZARD         2008/98/EC  LABELS
CODE                                 STATEMENTS     CODE

H203   EXPLOSIVES       DIVISION     EXPLOSIVE,     N/A         FLAME OVER
                        1.3          FIRE, BLAST                CIRCLE
                                     OR PROJECTION
                                     HAZARD


SECTION 3: COMPOSITION/INFORMATION ON INGREDIENTS(2) 


MATERIAL                                   CAS NO          (1)BY WEIGHT%

SPECIFIC CHEMICAL IDENTITY: LEAD           7439-92-1       APPROX. 57%
COMMON NAME: GRID

SPECIFIC CHEMICAL IDENTITY: LEAD DIOXIDE   1309-60-0       APPROX. 22%
COMMON NAME: LEAD OXIDE

SPECIFIC CHEMICAL IDENTITY: SULFURIC ACID  7664-93-9       APPROX. 14%
COMMON NAME: (3)BATTERY ELECTROLYTE
(ACID)

(4)PLASTIC CONTAINER/PLASTIC PARTS                         APPROX. 7%

1) CONTENTS MAY VARY DUE TO PERFORMANCE DATA OF THE BATTERY

2) SEE SECTION 12 - ECOLOGICAL INFORMATION

3) DENSITY OF THE ELECTROLYTE VARIES IN ACCORDANCE TO THE STATE OF CHARGE

4) COMPOSITION OF THE PLASTIC MAY VARY DUE TO DIFFERENT CUSTOMER
REQUIREMENTS


SECTION 4: FIRST AID MEASURES 


4.1 DESCRIPTION OF FIRST AID MEASURES:

ELECTROLYTE (DILUTED SULPHURIC ACID):
SULPHURIC ACID ACTS CORROSIVELY AND DAMAGES SKIN

LEAD COMPOUNDS:
LEAD COMPOUNDS ARE CLASSIFIED AS TOXIC FOR REPRODUCTION (IF SWALLOWED)

4.1.1 ELECTROLYTE (SULPHURIC ACID):

AFTER SKIN CONTACT: RINSE WITH WATER, REMOVE AND WASH WETTED CLOTHING

AFTER INHALATION OF ACID MIST:
INHALE FRESH AIR, SEEK ADVICE OF A MEDICAL DOCTOR

AFTER CONTACT WITH THE EYES:
RINSE UNDER RUNNING WATER FOR SEVERAL MINUTES, SEEK ADVICE OF A MEDICAL
DOCTOR

AFTER SWALLOWING:
DRINK LOT OF WATER IMMEDIATELY, SWALLOW ACTIVATED CARBON, DO NOT INDUCE
VOMITING, SEEK ADVICE OF A MEDICAL DOCTOR

4.1.2 LEAD COMPOUNDS:

AFTER SKIN CONTACT: CLEAN WITH WATER AND SOAP

AFTER INHALATION: INHALE FRESH AIR, SEEK ADVICE OF A MEDICAL DOCTOR

AFTER CONTACT WITH THE EYES:
RINSE UNDER RUNNING WATER FOR SEVERAL MINUTES, SEEK ADVICE OF A MEDICAL
DOCTOR

AFTER SWALLOWING: WASH MOUTH WITH WATER, SEEK ADVICE OF A MEDICAL DOCTOR


SECTION 5: FIREFIGHTING MEASURES 


UNUSUAL FIRE AND EXPLOSION HAZARDS:
HYDROGEN AND OXYGEN GASES ARE PRODUCED IN CELLS DURING NORMAL BATTERY
OPERATION AND EXPEL INTO AIR THROUGH VENT CAPS.

SUITABLE FIRE EXTINGUISHING AGENTS: CO2 OR DRY POWDER EXTINGUISHING AGENTS

UNSUITABLE FIRE EXTINGUISHING AGENTS:
WATER, IF THE BATTERY VOLTAGE IS ABOVE 120 V

SPECIAL PROTECTIVE EQUIPMENT:
PROTECTIVE GOGGLES, RESPIRATORY PROTECTIVE EQUIPMENT, ACID PROTECTIVE
EQUIPMENT, ACID PROOF CLOTHING IN CASE OF LARGER STATIONARY BATTERY PLANTS
OR WHERE LARGER QUANTITIES ARE STORED.

SPECIAL FIREFIGHTER PROCEDURES:
USE POSITIVE PRESSURE, SELF-CONTAINED BREATHING APPARATUS.

NOTE:
HYDROGEN FLASH POINT: -259 DEG. C.
HYDROGEN AUTO IGNITION POINT: 580 DEG. C

HYDROGEN FLAMMABLE LIMITS IN AIR (% BY VOLUME):
LOWER EXPLOSION LIMIT (LEL): 4.1
UPPER EXPLOSION LIMIT (UEL): 74.2


SECTION 6: ACCIDENTAL RELEASE MEASURES 


6.1 PERSONAL PRECAUTIONS, PROTECTIVE EQUIPMENT AND EMERGENCY PROCEDURES:

EYE PROTECTION:
CHEMICAL GOGGLES, SAFETY GLASSES WITH SIDE SHIELDS AND OR A FULL-FACE
SHIELD.

PROTECTIVE GLOVES: RUBBER, PVC OR NEOPRENE

RESPIRATORY PROTECTION:
NIOSH APPROVED ACID MIST/ORGANIC VAPOR RESPIRATOR, IF OSHA PEL IS EXCEEDED.

OTHER PROTECTIVE EQUIPMENT: ACID RESISTANT APRON OR CLOTHES.

NOTE:
PERSONAL PROTECTIVE EQUIPMENT ADVICE IS CONTAINED IN SECTION 8 OF THE SDS.

6.2 ENVIRONMENTAL PRECAUTIONS:
PREVENT ENTRY INTO WATERWAYS, SEWERS, BASEMENTS OR CONFINED AREAS. RUNOFF
FROM FIRE CONTROL AND DILUTION WATER MAY BE TOXIC AND CORROSIVE AND MAY
CAUSE ADVERSE ENVIRONMENTAL IMPACTS.

6.3 METHODS AND MATERIALS FOR CONTAINMENT AND CLEANING UP:

6.3.1 FOR CONTAINMENT:
IN THE EVENT OF A BATTERY RUPTURING; STOP THE LEAK IF YOU CAN DO IT WITHOUT
RISK. ABSORB WITH EARTH, SAND OR OTHER NON-COMBUSTIBLE MATERIAL. CAUTIOUSLY
NEUTRALIZE SPILLED LIQUID.

6.3.2 FOR CLEANING UP:
DISPOSE OF IN ACCORDANCE WITH LOCAL, STATE, AND NATIONAL REGULATIONS.


SECTION 7: HANDLING AND STORAGE 


7.1 PRECAUTIONS FOR SAFE HANDLING:

HANDLING:
KEEP AWAY FROM HEAT AND SOURCES OF IGNITION.

WASH HANDS THOROUGHLY AFTER USE.

DO NOT USE ORGANIC SOLVENTS; USE ONLY MANUFACTURER RECOMMENDED CLEANERS ON
THE BATTERIES.

AVOID SPARKS.

DO NOT REMOVE VENT CAPS.

DO NOT DOUBLE STACK INDUSTRIAL BATTERIES, IT MAY CAUSE DAMAGE.

STORAGE:
STORE BATTERIES IN A COOL, DRY AREA. STORE BATTERIES IN A COVERED AREA THAT
PROTECTS AGAINST ADVERSE WEATHER CONDITIONS. PROTECT BATTERIES FROM COMING
INTO CONTACT WITH CONDUCTIVE MATERIALS TO PREVENT FIRE OR BATTERY FAILURES.
DON'T STORE OR CHARGE BATTE RIES IN TEMPERATURES UNDER -4 DEG. F
(-20 DEG. C). KEEP AWAY FROM FIRE, SPARKS AND HEAT SOURCES. PROTECT FROM
DAMAGE TO PREVENT POSSIBLE LEAKS OR SPILLS. IT IS IMPERATIVE THAT THESE
INSTRUCTIONS BE FOLLOWED IF THE BATTERIES ARE BEING STORED.


SECTION 8: EXPOSURE CONTROLS/PERSONAL PROTECTION 


8.1 APPROPRIATE ENGINEERING CONTROLS:
STORE BATTERIES WITH ADEQUATE VENTILATION. ROOM VENTILATION IS ALSO
REQUIRED FOR BATTERIES UTILIZED FOR STANDBY POWER GENERATION. NEVER
RECHARGE BATTERIES IN AN UNVENTILATED, ENCLOSED SPACE.

SUBSTANCE  EC-NO.     CAS-NO     DESCRIPTION
NAME

LEAD       231-100-4  7439-92-1  NO EXPOSURE TO LEAD AND LEAD CONTAINING
                                 PASTE DURING NORMAL CONDITIONS OF USE.

SULFURIC   231-639-5  7664-93-9  R35: CAUSES SEVERE CHEMICAL BURNS
ACID
                                 S2: KEEP OUT OF REACH OF CHILDREN

                                 S16:
                                 KEEP AWAY FROM SPARKS OR NAKED FLAME, NO
                                 SMOKING

                                 S26:
                                 IN CASE OF CONTACT WITH EYES RINSE
                                 IMMEDIATELY WITH PLENTY OF WATER AND SEEK
                                 MEDICAL ADVICE

                                 S45:
                                 IN CASE OF ACCIDENT OR IF YOU FEEL UNWELL
                                 SEEK MEDICAL ADVICE IMMEDIATELY (SHOW THE
                                 LABEL WHERE POSSIBLE).

8.2 INDIVIDUAL PROTECTION MEASURES:

PERSONAL PROTECTIVE EQUIPMENT:
DURING INSTALLATION UNDER NORMAL CONDITIONS THERE IS NO EXPOSURE TO LEAD OR
SULPHURIC ACID. IN THE EVENT OF BATTERY BREAKAGE, EXPOSURE TO SULPHURIC
ACID AND LEAD MAY OCCUR. DURING HIGH RATE CHARGES OR OVERCHARGING ACID MIST
MAY OCCUR.

EYE/FACE PROTECTION:
CHEMICAL GOGGLES, SAFETY GLASSES WITH SIDE SHIELDS AND OR A FULL-FACE
SHIELD.

PROTECTIVE GLOVES: RUBBER, PVC OR NEOPRENE

RESPIRATORY PROTECTION:
NIOSH APPROVED ACID MIST/ORGANIC VAPOR RESPIRATOR, IF OSHA PEL IS EXCEEDED.

OTHER PROTECTIVE EQUIPMENT: ACID RESISTANT APRON OR CLOTHES.


SECTION 9: PHYSICAL AND CHEMICAL PROPERTIES 


ITEM                       LEAD AND LEAD                ELECTROLYTE
                           COMPOUNDS

APPEARANCE:

FORM                       SOLID                        LIQUID

COLOR                      GREY                         COLORLESS

ODOR                                         ODORLESS

PH                                           N/A

MELTING POINT/FREEZING     327.4 DEG. C                 -35 TO -60 DEG. C
POINT.                     (MELTING POINT)

INITIAL BOILING POINT      1740 DEG. C                  APPROX. 108-114
AND BOILING RANGE.         (LIT.)                       DEG. C

FLASH POINT.                                 N/A

EVAPORATION RATE.                            N/A

VAPOR PRESSURE.            N.A.                         <0.3 MMHg
(MMHg AT 20 DEG. C)

VAPOR DENSITY. (AIR=1)     7.1                          3.4

DENSITY (20 DEG. C)        11.35 G/CM3                  1.2 TO 1.3 G/CM3

SOLUBILITY IN WATER        VERY LOW                     FULLY SOLUBLE
                           (0.15 MG/L)

PARTITION COEFFICIENT                        N/A
N-OCTANOL/WATER.

DECOMPOSITION                                N/A
TEMPERATURE.

LEAD AND LEAD COMPOUNDS USED IN LEAD ACID BATTERIES ARE POORLY SOLUBLE IN
WATER

LEAD CAN BE DISSOLVED IN AN ACIDIC OR ALKALINE ENVIRONMENT ONLY

WORK PRACTICES:
USE STANDARD LEAD-ACID BATTERY PRACTICES. DO NOT WEAR METALLIC JEWELRY WHEN
WORKING WITH BATTERIES. USE NON-CONDUCTIVE TOOLS ONLY. DISCHARGE STATIC
ELECTRICITY PRIOR TO WORKING ON A BATTERY. MAINTAIN EYEWASH, FIRE
EXTINGUISHER AND EMERGENCY COMMUNICATION DEVICE.


SECTION 10: STABILITY AND REACTIVITY 


10.1 REACTIVITY:
BROKEN BATTERIES MAY RESULT IN SMALL AMOUNTS OF SPILLED ELECTROLYTE.
ELECTROLYTE IS A CORROSIVE, NONFLAMMABLE LIQUID. ELECTROLYTE CAN DESTROY
ORGANIC MATERIALS SUCH AS CARDBOARD, WOOD, TEXTILES. ELECTROLYTE MAY
PRODUCE HYDROGEN AS A REACTION WITH SOME METALS.

10.2 CHEMICAL STABILITY:
THE BATTERY AND CONTENTS ARE STABLE UNDER NORMAL CONDITIONS.

10.3 POSSIBILITY OF HAZARDOUS REACTIONS:
HAZARDOUS POLYMERIZATION WILL NOT OCCUR.

10.4 CONDITIONS TO AVOID:
OVERHEATING OR OVERCHARGING THE BATTERY MAY RESULTS IN ACID MIST AND
HYDROGEN GENERATION.

10.5 INCOMPATIBILITY (MATERIALS TO AVOID):
STRONG ALKALINE MATERIALS, CONDUCTIVE METALS, ORGANIC SOLVENTS, SPARK OR
OPEN FLAME.

10.6 HAZARDOUS DECOMPOSITION PRODUCTS:
HYDROGEN GAS MAY BE GENERATED IN AN OVERCHARGED CONDITION, IN FIRE OR AT
VERY HIGH TEMPERATURES. IN FIRE, MAY EMIT CO, CO2 AND SULFUR OXIDES.


SECTION 11: TOXICOLOGICAL INFORMATION 


11.1 INFORMATION ON TOXICOLOGICAL EFFECTS:
CSB VRLA BATTERIES ARE SEALED, RECOMBINANT DESIGN THAT REQUIRE NO WATER
REPLACEMENT THROUGHOUT THEIR SERVICE LIFE, THUS NO CONTACT IS MADE WITH THE
BATTERY'S INTERNAL COMPONENTS OR CHEMICAL HAZARDS. UNDER NORMAL USE AND
HANDLING, THESE BATTERIES DO NOT EMI T REGULATED OR HAZARDOUS SUBSTANCES.

SULFURIC ACID (7664-93-9):

ADMINISTRATION ROUTE              METHOD      DOSE           TEST ANIMAL

ACUTE ORAL TOXICITY               LD50        2140 MG/KG     RAT

ACUTE INHALATIVE TOXICITY         LC50        510 MG/M3      RAT
(VAPOR)

11.2 ROUTES OF EXPOSURE:

               ACUTE                             CHRONIC

INHALATION     UNDER NORMAL CONDITIONS OF USE,   REPEATED AND PROLONGED
               NO HEALTH EFFECTS ARE EXPECTED.   EXPOSURE MAY CAUSE
               CONTENTS OF AN OPEN BATTERY       IRRITATION.
               CAN CAUSE RESPIRATORY
               IRRITATION.

SKIN           UNDER NORMAL CONDITIONS OF USE,   NO DATA AVAILABLE
               NO HEALTH EFFECTS ARE EXPECTED.

EYE            UNDER NORMAL CONDITIONS OF USE,   NO DATA AVAILABLE.
               NO HEALTH EFFECTS ARE EXPECTED.
               EXPOSURE TO DUST MAY CAUSE
               IRRITATION.

INGESTION      UNDER NORMAL CONDITIONS OF USE,   NO DATA AVAILABLE
               NO HEALTH EFFECTS ARE EXPECTED.
               LEAD INGESTION MAY CAUSE
               ABDOMINAL PAIN, NAUSEA,
               VOMITING, DIARRHEA AND SEVERE
               CRAMPING.


SECTION 12: ECOLOGICAL INFORMATION 


THIS INFORMATION IS OF RELEVANCE IF THE BATTERY IS BROKEN AND THE
INGREDIENTS ARE RELEASED TO ENVIRONMENT.

12.1 ELECTROLYTE (DILUTED SULPHURIC ACID):
IN ORDER TO AVOID DAMAGE TO THE SEWAGE SYSTEM, THE ACID HAS TO BE
NEUTRALIZED BY MEANS OF TIME OR SODIUM CARBONATE BEFORE DISPOSAL.
ECOLOGICAL DAMAGE IS POSSIBLE BY CHANGE OF PH. THE ELECTROLYTE SOLUTION
REACTS WITH WATER AND ORGANIC SUBSTANCES, CAUSING DAMAGE TO FLORA AND
FAUNA. THE ELECTROLYTE MAY ALSO CONTAIN SOLUBLE COMPONENTS OF LEAD THAT CAN
BE TOXIC TO AQUATIC ENVIRONMENTS.

12.2 LEAD AND LEAD COMPOUNDS:
CHEMICAL AND PHYSICAL TREATMENT IS REQUIRED FOR THE ELIMINATION FROM WATER.
WASTE WATER CONTAINING LEAD MUST NOT BE DISPOSED OF IN AN UNTREATED
CONDITION. THE FORMER CLASSIFICATION OF LEAD COMPOUNDS AS TOXIC FOR THE
AQUATIC ENVIRONMENT R50/53 HAD BEEN TRIGGERED FROM TEST RESULTS GENERATED
IN THE 80'S FOR SOLUBLE LEAD COMPOUNDS (LEAD ACETATE). THE HARDLY SOLUBLE
LEAD COMPOUNDS SUCH AS BATTERY LEAD OXIDE WERE NOT TESTED AT THIS TIME.
TESTS ON BATTERY LEAD OXIDE WERE CARRIED OUT IN 2001 AND 2005. THE
RESPECTIVE TEST RESULTS CONCLUDE THAT BATTERY LEAD OXIDE IS NOT TOXIC FOR
THE ENVIRONMENT, NEITHER R50 NOR R50/53 NOR R51/53. FROM THIS IT FOLLOWS
THAT THE GENERAL CLASSIFICATION FOR LEAD COMPOUNDS (R50/53) DOES NOT APPLY
TO BATTERY LEAD OXIDE. AS THE RESULT OF THIS THE RISK PHRASE R52/53
(HARMFUL TO AQUATIC ORGANISMS, MAY CAUSE LONGTERM ADVERSE EFFECTS IN THE
AQUATIC ENVIRONMENT) APPLIES TO BATTERY LEAD OXIDE.

EFFECTS OF BATTERY LEAD OXIDE IN THE AQUATIC ENVIRONMENT:

TOXICITY FOR FISH:
96 H LC50: >100 MG/L

TOXICITY FOR DAPHNIA:
48 H EC50: >100 MG/L

TOXICITY FOR ALGA:
72 H IC50: >10 MG/L

THE RESULTS DEMONSTRATE THESE BATTERY LEAD OXIDE COMPOUNDS IN A
CONCENTRATION OF 100 MG/L HAVE NO ADVERSE EFFECT ON FISH AND DAPHNIA. A
CONCENTRATION OF THESE BATTERY LEAD OXIDE OF 10 MG/L HAS NO ADVERSE EFFECT
ON THE RATE OF GROWTH AND THE BIOMASS. FOR THE CLASSIFICATION ACCORDING TO
DIRECTIVE 67/548/EEC THE MOST SENSITIVE ADVERSE EFFECT HAS TO BE
CONSIDERED. AS A RESULT OF THE TOXICITY FOR ALGA AT >10 MG/L BATTERY LEAD
OXIDE HAS TO BE CLASSIFIED ACCORDING TO THE R-PHRASES 52/53 (HARMFUL TO
AQUATIC ORGANISMS, MAY CAUSE LONG TERM ADVERSE EFFECTS IN THE AQUATIC
ENVIRONMENT).

CARCINOGENICITY:
THE INTERNATIONAL AGENCY ON CANCER (IARCC) HAS CLASSIFIED "STRONG
INORGANIC ACID MISTS CONTAINING SULFURIC ACID" AS A CATEGORY 1 CARCINOGEN
(INHALATION), A SUBSTANCE THAT IS CARCINOGENIC TO HUMANS. THIS
CLASSIFICATION DOES NOT APPLY TO THE LIQUID FORMS OF SULFURIC ACID
CONTAINED WITHIN THE BATTERY. MISUSE OF THE PRODUCT, SUCH AS OVERCHARGING,
MAY RESULT IN THE GENERATION OF SULFURIC ACID MIST AT HIGH LEVELS.


SECTION 13: DISPOSAL CONSIDERATIONS 


SPENT LEAD ACID BATTERIES (EWC 160601) ARE SUBJECT TO REGULATION OF THE EU
BATTERY DIRECTIVE AND ITS ADOPTIONS INTO NATIONAL LEGISLATION ON THE
COMPOSITION AND END OF LIFE MANAGEMENT OF BATTERIES.

SPENT LEAD ACID BATTERIES ARE RECYCLED IN LEAD REFINERIES (SECONDARY LEAD
SMELTERS). THE COMPONENTS OF A SPENT LEAD ACID BATTERY ARE RECYCLED OR
REPROCESSED.

AT THE POINTS OF SALE, THE MANUFACTURERS AND IMPORTERS OF BATTERIES,
RESPECTIVELY THE METAL DEALERS TAKE BACK SPENT BATTERIES, AND RENDER THEM
TO THE SECONDARY LEAD SMELTERS FOR PROCESSING.

TO SIMPLIFY THE COLLECTION AND RECYCLING OR REPROCESSING PROCESS SPENT LEAD
ACID BATTERIES MUST NOT BE MIXED WITH OTHER BATTERIES. BY NO MEANS MAY THE
ELECTROLYTE (DILUTED SULPHURIC ACID) BE EMPTIED IN AN INEXPERT MANNER. THIS
PROCESS IS TO BE CARRIED OUT BY THE PROCESSING COMPANIES ONLY.


SECTION 14: TRANSPORT INFORMATION 


ALL CSB BATTERIES ARE IDENTIFIED AS "BATTERY, ELECTRIC STORAGE, WET,
NONSPILLABLE" WHEN TRANSPORTED BY AIR, SEA OR BY LAND TRANSPORTATION. THE
BATTERY(S) MUST BE IDENTIFIED AS ABOVE ON THE BILL OF LADING AND PROPERLY
PACKAGED WITH THEIR TERMINALS PROTECTED FROM SHORT CIRCUIT. NA OR UN
NUMBERS DO NOT APPLY. CSB BATTERY(S) WARNING LABEL IDENTIFIES EACH BATTERY
AS NONSPILLABLE.

CSB SEAL LEAD-ACID BATTERIES ARE CLASSIFIED AS "NONSPILLABLE" FOR THE
PURPOSE OF TRANSPORTATION BY DOT, AND IATA/ICAO AS RESULT OF PASSING THE
VIBRATION AND PRESSURE DIFFERENTIAL TEST DESCRIBED IN DOT [49 CFR 173.159
(F)] AND IATA/ICAO [SPECIAL PROVISION A67].CSB SEAL LEAD-ACID BATTERIES CAN
BE SAFELY TRANSPORTED ON DECK, OR UNDER DECK STORED ON EITHER A PASSENGER
OR CARGO VESSEL AS RESULT OF PASSING THE VIBRATION AND PRESSURE
DIFFERENTIAL TESTS AS DESCRIBED IN THE IMDG REGULATIONS(SPECIAL ARTICLE
238).

TO TRANSPORT THESE BATTERIES AS "NON-SPILLABLE" THEY MUST BE SHIPPED IN A
CONDITION THAT WOULD PROTECT THEM FROM SHORT-CIRCUITS AND BE SECURELY
PACKAGED SO AS TO WITHSTAND CONDITIONS NORMAL TO TRANSPORTATION BY A
CONSUMER, IN OR OUT OF A DEVICE, THEY ARE UNREGULATED THUS REQUIRING NO
ADDITIONAL SPECIAL HANDLING OR PACKAGING.

FOR ALL MODES OF TRANSPORTATION, EACH BATTERY AND OUTER PACKAGE IS LABELED
"NON-SPILLABLE" PER 49 CFR 173.159(F) AND 49 CFR 173.159A. IF YOU REPACKAGE
OUR BATTERIES EITHER AS BATTERIES OR AS A COMPONENT OF ANOTHER PRODUCT YOU
MUST LABEL THE OUTER PACKAGE "NON-SPILLABLE" PER 49 CFR 173.159(F) AND 49
CFR 173.159A.


SECTION 15: REGULATORY INFORMATION 


IN ACCORDANCE WITH EU BATTERY DIRECTIVE AND THE RESPECTIVE NATIONAL
LEGISLATION, LEAD ACID BATTERIES HAVE TO BE MARKED BY A CROSSED OUT DUST
BIN WITH THE CHEMICAL SYMBOL FOR LEAD SHOWN BELOW, TOGETHER WITH THE ISO
RETURN/RECYCLING SYMBOL.

PB

IN ADDITION SOME OF THE FOLLOWING HAZARD SYMBOLS DESCRIBED BELOW MIGHT
APPLY:
CORROSIVE
EXPLOSIVE GAS MIXTURE
READ INSTRUCTIONS
KEEP OUT OF REACH OF CHILDREN
NO SMOKING, NO OPEN FLAMES, NO SPARKS.
WEAR SAFETY GOGGLES

15.1 STATE REGULATIONS (US):

CALIFORNIA PROPOSITION 65 WARNING:
BATTERY POSTS, TERMINALS AND RELATED ACCESSORIES CONTAIN LEAD AND LEAD
COMPOUNDS, CHEMICALS KNOWN TO THE STATE OF CALIFORNIA TO CAUSE CANCER AND
REPRODUCTIVE HARM. WASH HANDS AFTER HANDLING.

15.2 INTERNATIONAL REGULATIONS (NON-US):

NATIONAL REGULATIONS(CANADA):

CANADIAN DOMESTIC SUBSTANC LIST (DSL):
ALL INGREDIENTS REMAINING IN THE FINISHED PRODUCT AS DISTRIBUTED INTO
COMMERCE ARE INCLUDED ON THE DOMESTIC SUBSTANCES LIST.

CANADA NDSL:
NONE OF THE COMPONENTS ON THIS SDS ARE LISTED ON THE CANADIAN NDSL

WHMIS CLASSIFICATIONS:

CLASS E: CORROSIVE MATERIALS PRESENT AT GREATER THAN 1%

THIS PRODUCT HAS BEEN CLASSIFIED IN ACCORDANCE WITH THE HAZARD CRITERIA OF
THE CONTROLLED PRODUCTS REGULATIONS (CPR) AND THE SDS CONTAINS ALL THE
INFORMATION REQUIRED BY THE CONTROLLED PRODUCTS REGULATIONS.

ABOUT BATTERY HANDLING, PLEASE SEE THE OSHA 29 CFR 1910.268(B) AS BELOW:

910.268(B)(2)(I):
EYE PROTECTION DEVICES WHICH PROVIDE SIDE AS WELL AS FRONTAL EYE PROTECTION
FOR EMPLOYEES SHALL BE PROVIDED WHEN MEASURING STORAGE BATTERY SPECIFIC
GRAVITY OR HANDLING ELECTROLYTE AND THE EMPLOYER SHALL ENSURE THAT SUCH
DEVICES ARE USED BY THE EMPLOYEES. THE EMPLOYER SHALL ALSO ENSURE THAT ACID
RESISTANT GLOVES AND APRONS SHALL BE WORN FOR PROTECTION AGAINST
SPATTERING. FACILITIES FOR QUICK DRENCHING OR FLUSHING OF THE EYES AND BODY
SHALL BE PROVIDED UNLESS THE STORAGE BATTERIES ARE OF THE ENCLOSED TYPE AND
EQUIPPED WITH EXPLOSION PROOF VENTS, IN WHICH CASE SEALED WATER RINSE OR
NEUTRALIZING PACKS MAY BE SUBSTITUTED FOR THE QUICK DRENCHING OR FLUSHING
FACILITIES. EMPLOYEES ASSIGNED TO WORK WITH STORAGE BATTERIES SHALL BE
INSTRUCTED IN EMERGENCY PROCEDURES SUCH AS DEALING WITH ACCIDENTAL ACID
SPILLS.

1910.268(B)(2)(II):
ELECTROLYTE (ACID OR BASE, AND DISTILLED WATER) FOR BATTERY CELLS SHALL BE
MIXED IN A WELL VENTILATED ROOM. ACID OR BASE SHALL BE POURED GRADUALLY,
WHILE STIRRING, INTO THE WATER. WATER SHALL NEVER BE POURED INTO
CONCENTRATED (GREATER THAN 75 PERCENT) ACID SOLUTIONS. ELECTROLYTE SHALL
NEVER BE PLACED IN METAL CONTAINERS NOR STIRRED WITH METAL OBJECTS.

1910.268(B)(2)(III):
WHEN TAKING SPECIFIC GRAVITY READINGS, THE OPEN END OF THE HYDROMETER SHALL
BE COVERED WITH AN ACID RESISTANT MATERIAL WHILE MOVING IT FROM CELL TO
CELL TO AVOID SPLASHING OR THROWING THE ELECTROLYTE.


SECTION 16: OTHER INFORMATION 


PRODUCTS SUCH AS BATTERIES ARE NOT IN THE SCOPE OF REGULATION WHICH
REQUIRES THE PUBLICATION OF AN EU SAFETY DATA SHEET (91/155/EEC).

THE INFORMATION GIVEN ABOVE IS PROVIDED IN GOOD FAITH BASED ON EXISTING
KNOWLEDGE AND DOES NOT CONSTITUTE AN ASSURANCE OF SAFETY UNDER ALL
CONDITIONS. IT IS THE USER'S RESPONSIBILITY TO OBSERVE ALL LAWS AND
REGULATIONS APPLICABLE FOR STORAGE, USE, MAINTE NANCE OR DISPOSAL OF THE
PRODUCT. IF THERE ARE ANY QUERIES, THE SUPPLIER SHOULD BE CONSULTED.

HOWEVER, THIS SHALL NOT CONSTITUTE A GUARANTEE FOR ANY SPECIFIC PRODUCT
FEATURES AND SHALL NOT ESTABLISH A LEGALLY VALID CONTRACTUAL RELATIONSHIP.
THE CONTENTS AND FORMAT OF THIS SDS ARE IN ACCORDANCE WITH EEC COMMISSION
DIRECTIVE 1999/45/EC, 67/548/EC, 1272/2008/EC AND EEC COMMISSION REGULATION
1907/2006/EC (REACH) ANNEX II.