SDS Table of Contents Click the desired link below to jump directly to that section in the SDS. MSDS FOR SLA BATTERIES UPG LET US POWER YOU.(R*)
VALVE REGULATED LEAD-ACID BATTERIES.
COMPONENTS %WEIGHT TLV LD50 ORAL LC50 LC50 INHALATION CONTACT LEAD ABOUT 70% N/A (500) MG/KG N/A N/A (Pb, PbO2, PbSO4) SULFURIC ACID ABOUT 20% 1 MG/M3 (2.140) MG/KG N/A N/A FIBERGLASS ABOUT 5% N/A N/A N/A N/A SEPARATOR ABS OR PP ABOUT 5% N/A N/A N/A N/A
COMPONENTS DENSITY MELTING POINT SOLUBILITY ODOR APPEARANCE (H2O) LEAD 11.34 327.4 DEG. C NONE NONE SILVER-GREY (BOILING) METAL LEAD SULFATE 6.2 1070 DEG. C 40 MG/L NONE WHITE POWDER (BOILING) (15 DEG. C) LEAD DIOXIDE 9.4 290 DEG. C NONE NONE BROWN POWDER (BOILING) SULFURIC ABOUT 1.3 ABOUT 100% ACIDIC CLEAR ACID 114 DEG. C COLORLESS (BOILING) LIQUID FIBERGLASS N/A N/A SLIGHT TOXIC WHITE FIBROUS SEP. GLASS ABS OR PP N/A N/A NONE NO ODOR SOLID
EXPOSURE PROTECTION COMMENTS SKIN RUBBER GLOVES, APRON, PROTECTIVE EQUIPMENT MUST BE SAFETY SHOES WORN IF BATTERY IS CRACKED OR OTHERWISE DAMAGED. RESPIRATORY RESPIRATOR (FOR LEAD) A RESPIRATOR SHOULD BE WORN DURING RECLAIM OPERATIONS IF THE TLV EXCEEDED. EYES SAFETY GOGGLES, FACE SHIELD
COMPONENTS FLASH POINT EXPLOSIVE LIMITS COMMENTS LEAD NONE NONE SULFURIC ACID NONE NONE HYDROGEN 259? 4% - 74.2% BATTERIES CAN EMIT HYDROGEN ONLY IF OVER CHARGED (FLOAT VOLTAGE> 2.4 VPC). THE GAS ENTERS THE AIR THROUGH THE VENT CAPS. TO AVOID THE CHANCE OF A FIRE OR EXPLOSION, KEEP SPARKS AND OTHER SOURCES OF IGNITION AWAY FROM THE BATTERY. EXTINGUISHING MEDIA: DRY CHEMICAL, FOAM, CO2. FIBERGLASS N/A N/A TOXIC VAPORS MAY BE RELEASED. SEP. IN CASE OF FIRE: WEAR SELF-CONTAINED BREATHING APPARATUS. 478 NONE N/A TEMPERATURES OVER 300 DEG. C POLYSTYRENE (572 DEG. F) MAY RELEASE COMBUSTIBLE GASES. IN CASE OF FIRE: WEAR POSITIVE PRESSURE SELF-CONTAINED BREATHING APPARATUS.
COMPONENT: LEAD/LEAD COMPOUNDS STABILITY: STABLE INCOMPATIBILITY: POTASSIUM, CARBIDES, SULFIDES, PEROXIDES, PHOSPHORUS, SULFURS. DECOMPOSITION PRODUCTS: OXIDES OF LEAD AND SULFUR. CONDITIONS TO AVOID: HIGH TEMPERATURE, SPARKS AND OTHER SOURCES OF IGNITION COMPONENT: SULFURIC ACID STABILITY: STABLE AT ALL TEMPERATURES POLYMERIZATION: WILL NOT POLYMERIZE INCOMPATIBILITY: REACTIVE METALS, STRONG BASES, MOST ORGANIC COMPOUNDS DECOMPOSITION PRODUCTS: SULFURIC DIOXIDE, TRIOXIDE, HYDROGEN SULFIDE, HYDROGEN CONDITIONS TO AVOID: PROHIBIT SMOKING, SPARKS, ETC. FROM BATTERY CHARGING AREA. AVOID MIXING ACID WITH OTHER CHEMICALS.
1. STORE LEAD/ACID BATTERIES WITH ADEQUATE VENTILATION. ROOM VENTILATION IS REQUIRED FOR BATTERIES UTILIZED FOR STANDBY POWER GENERATION. NEVER RECHARGE BATTERIES IN AN UNVENTILATED, ENCLOSED SPACE. 2. DO NOT REMOVE VENT CAPS. FOLLOW SHIPPING AND HANDLING INSTRUCTIONS THAT ARE APPLICABLE TO THE BATTERY TYPE. TO AVOID DAMAGE TO TERMINALS AND SEALS, DO NOT DOUBLE-STACK INDUSTRIAL BATTERIES. STEPS TO TAKE IN CASE OF LEAKS OR SPILLS: IF SULFURIC ACID IS SPILLED FROM A BATTERY, NEUTRALIZE THE ACID WITH SODIUM BICARBONATE (BAKING SODA), SODIUM CARBON (SODA ASH), OR CALCIUM OXIDE (LIME). FLUSH THE AREA WITH WATER DISCARD TO THE SEWAGE SYSTEMS. DO NOT ALLOW UNNEUTRALIZED ACID INTO THE SEWAGE SYSTEM. WASTE DISPOSAL METHOD: NEUTRALIZED ACID MAY BE FLUSHED DOWN THE SEWER. SPENT BATTERIES MUST BE TREATED AS HAZARDOUS WASTE AND DISPOSED OF ACCORDING TO LOCAL STATE, AND FEDERAL REGULATIONS. A COPY OF THIS MATERIAL SAFETY DATA MUST BE SUPPLIED TO ANY SCRAP DEALER OR SECONDARY SMELTER WITH BATTERY. ELECTRICAL SAFETY: DUE TO THE BATTERY'S LOW INTERNAL RESISTANCE AND HIGH POWER DENSITY; HIGH LEVELS OF CURRENT CAN BE DEVELOPED ACROSS THE BATTERY TERMINALS. DO NOT REST TOOLS OR CABLES ON THE BATTERY. USE INSULATED TOOLS ONLY. FOLLOW ALL INSTALLATION INSTRUCTION AND DIAGRAMS WHEN INSTALLING OR MAINTAINING BATTERY SYSTEMS.
LEAD: THE TOXIC EFFECTS OF LEAD ARE CUMULATIVE AND SLOW TO APPEAR. IT AFFECTS THE KIDNEYS, REPRODUCTIVE, AND CENTRAL NERVOUS SYSTEM. THE SYMPTOMS OF LEAD OVEREXPOSURE ARE ANEMIA, VOMITING, HEADACHE, STOMACH PAIN (LEAD COLIC), DIZZINESS, LOSS OF APPETITE, AND MUSCLE AND JOINT PAIN. EXPOSURE TO LEAD FROM A BATTERY MOST OFTEN OCCURS DURING LEAD RECLAIM OPERATIONS THROUGH THE BREATHING OR INGESTION OF LEAD DUSTS AND FUMES. THIS DATA MUST BE PASSED TO ANY SCRAP OR SMELTER WHEN A BATTERY IS RESOLD. SULFURIC ACID: SULFURIC ACID IS A STRONG CORROSIVE. CONTACT WITH ACID CAN CAUSE SEVERE BURNS ON THE SKIN AND IN THE EYES. INGESTION OF SULFURIC ACID WILL CAUSE GI TRACT BURNS. ACID CAN BE RELEASE IF THE BATTERY CASE IS DAMAGED OR IF THE VENTS ARE TAMPERED WITH. FIBERGLASS SEPARATOR: FIBROUS GLASS IS AN IRRITANT OF THE UPPER RESPIRATORY TRACT, SKIN AND EYES. FOR EXPOSURE UP TO 10F/CC USE MSA COMFORT WITH TYPE H FILTER. ABOVE 10F/CC UP TO 50F/CC USE ULTRA-TWIN WITH TYPE H FILTER. NTP OR OSHA DOES NOT CONSIDER THIS PRODUCT CARCINOGENIC.
INHALATION: ACID MIST FORM MAY CAUSE RESPIRATORY IRRITATION. REMOVE ANY INDIVIDUAL FROM EXPOSURE, AND APPLY OXYGEN IF BREATHING IS DIFFICULT. SKIN CONTACT: ACID MAY CAUSE IRRITATION, BURNS OR ULCERATION. FLUSH WITH PLENTY OF SOAP AND WATER, REMOVE CONTAMINATED CLOTHING, AND SEE PHYSICIAN IF CONTACT AREA IS LARGE OR IF BLISTERS FORM. EYE CONTACT: ACID MAY CAUSE SEVERE IRRITATION, BURNS, CORNEA DAMAGE AND BLINDNESS. CALL PHYSICIAN IMMEDIATELY AND FLUSH WITH WATER UNTIL PHYSICIAN ARRIVES. INGESTION: ACID MAY CAUSE IRRITATION OF MOUTH, THROAT, ESOPHAGUS AND STOMACH. CALL PHYSICIAN. IF PATIENT IS CONSCIOUS, FLUSH MOUTH WITH WATER, HAVE THE PATIENT DRINK MILK OR SODIUM BICARBONATE SOLUTION. DO NOT GIVE ANYTHING TO AN UNCONSCIOUS PERSON.
WE HEREBY CERTIFY THAT ALL UPG VALVE REGULATED LEAD-ACID RECHARGEABLE BATTERIES CONFORM TO THE UN2800 CLASSIFICATION AS "BATTERIES, WET, NON-SPILLABLE, AND ELECTRIC STORAGE" AS A RESULT OF PASSING THE VIBRATION AND PRESSURE DIFFERENTIAL TEST DESCRIBED IN D.O.T., 49 CFR 173.159(D), AND IMO/IMDG, AND ICAO/IATA PACKING INSTRUCTION 806 AND NOTE A67. BATTERIES HAVING MET THE RELATED CONDITIONS ARE EXEMPT FROM HAZARDOUS GOODS REGULATIONS FOR THE PURPOSE OF TRANSPORTATION BY DOT, AND IATA/ICAO, AND THEREFORE ARE UNRESTRICTED FOR TRANSPORTATION BY ANY MEANS. FOR ALL MODES OF TRANSPORTATION, EACH BATTERY OUTER PACKAGE IS LABELED "NON-SPILLABLE". ALL OUR BATTERIES ARE MARKED NON-SPILLABLE. UPDATED: FEB. 18, 2010 |